| 提交詢價(jià)信息 |
| 發(fā)布緊急求購(gòu) |
價(jià)格:電議
所在地:北京
型號(hào):UC-KB-2008D
更新時(shí)間:2016-06-29
瀏覽次數(shù):1637
公司地址:北京市通州區(qū)永順西街32號(hào)
![]()
周先生(先生) 經(jīng)理
UC-KB-2008D型
氣體報(bào)警控制器
使用說明書
目 錄
1. 引言·····························································2
1.1 簡(jiǎn)述·······················································2
1.2 技術(shù)指標(biāo)···················································2
1.3 主要功能···················································2
2. 安裝····························································3
2.1 安裝尺寸···················································3
2.2 接線·······················································4
2.3 開通························································4
3. 操作說明························································5
3.1 面板說明···················································5
3. 2 工作狀態(tài)說明···············································6
4. 使用調(diào)整························································9
5. 報(bào)警處理························································9
6. 故障診斷與處理··················································10
7. 維護(hù)維修 ·······················································10
8. UC-KT-2021型氣體探測(cè)器說明書····································11
1.引言
本手冊(cè)分兩部分,分別詳細(xì)介紹了UC-KB-2008D型氣體報(bào)警控制器(見圖1)及UC-KT-2021型氣體探測(cè)器的安裝,操作及維護(hù)。在使用和安裝前請(qǐng)仔細(xì)閱讀本手冊(cè)。
1.1 簡(jiǎn)述
UC-KB-2008D型氣體報(bào)警控制器(以下簡(jiǎn)稱控制器),它與(4~20)mA標(biāo)準(zhǔn)信號(hào)氣體探測(cè)器(以下簡(jiǎn)稱探測(cè)器)配合使用。探測(cè)器固定安裝在可能有氣體泄露的室內(nèi)、外危險(xiǎn)場(chǎng)所??刂破鹘邮芴綔y(cè)器傳來的電信號(hào),并對(duì)之進(jìn)行濾波、模數(shù)轉(zhuǎn)換、線性化、濃度計(jì)算等一系列處理工作,得到當(dāng)前所測(cè)氣體的濃度值。當(dāng)濃度值達(dá)到預(yù)先設(shè)定的報(bào)警值時(shí),控制器即可發(fā)出聲、光報(bào)警及控制信號(hào),提示操作人員采取安全對(duì)策或自動(dòng)啟動(dòng)相關(guān)設(shè)備,從而避免發(fā)生爆炸事故??刂破骶哂斜容^完善的自診斷功能,可對(duì)系統(tǒng)的各種故障進(jìn)行處理,以便及時(shí)維修。
控制器設(shè)計(jì)符合國(guó)標(biāo)GB16808-1997《可燃?xì)怏w報(bào)警控制器技術(shù)要求和試驗(yàn)方法》,經(jīng)過公安部消防產(chǎn)品合格評(píng)定中心評(píng)定,獲得產(chǎn)品型式認(rèn)可證書,編號(hào):ROS。經(jīng)過北京市相關(guān)質(zhì)量技術(shù)監(jiān)督部門的考核,獲得制造計(jì)量器具許可證,證號(hào):京[制]01120010號(hào)。
1.2 技術(shù)指標(biāo)
供電電壓:交流(187~242)V
線性誤差限:±5% F.S
功 耗: <50W [與通道容量有關(guān)]
工作溫度:(0~40)℃
工作濕度:≤95%
通道容量:[本機(jī)為12點(diǎn)]
報(bào)警設(shè)置:高、低限報(bào)警兩級(jí)報(bào)警
觸點(diǎn)輸出:高、低限報(bào)警各有1組無源常開觸點(diǎn)(電容量220VAC 2A)
傳輸距離:≤1km(線阻小于20Ω)
箱體規(guī)格:[見圖1]
重 量:[與通道容量有關(guān)]
1.3 主要功能
1.高、低限報(bào)警各對(duì)應(yīng)相應(yīng)的聯(lián)動(dòng)輸出。
2. 控制器具有自檢功能,可對(duì)機(jī)器的重要部件和面板上所有指示燈進(jìn)行檢查。
3. 帶有散熱裝置。
4.當(dāng)有下列情形之一時(shí),控制器能在30s內(nèi)發(fā)出與報(bào)警信號(hào)有明顯區(qū)別的聲、光故障信號(hào):
a. 探測(cè)器與控制器連接線斷路。
b. 探測(cè)器內(nèi)部元件失效。
c. 控制器主要元件失效。
2 安裝
2.1 安裝尺寸(如圖1)
圖1 控制器外觀尺寸 圖2 控制器接線說明
2.2接線
控制器的后端蓋,可見如圖2 、圖3的接線端子板、電源插座。
A. 插座所帶電源線連接到外部電源,將內(nèi)部電源線插于插座上。并查看插座開關(guān)是否開啟。
B.直流電源線 [V+、V-]:V+、V-為24V直流電輸出端。
C.信號(hào)線:信號(hào)線采用3芯儀表用控制電纜,與探測(cè)器相連,線徑及傳輸距離見表1。將控制器上的P,S,G分別與探測(cè)器的P,S,G相連。
表1 線徑及傳輸距離
|
電纜橫截面(mm) |
0.75 |
1.0 |
1.5 |
|
遠(yuǎn)傳輸距離(M) |
500 |
750 |
1000 |
圖3控制器單個(gè)接線板示意圖
注意: 1、控制器與探測(cè)器連接時(shí),注意控制器P,S,G與探測(cè)器P,S,G相對(duì)應(yīng),切勿接反!
2、安裝布線工程應(yīng)符合GB 50093-2002《工業(yè)自動(dòng)化儀表施工
3、驗(yàn)收規(guī)范》或《中華人民共和國(guó)危險(xiǎn)場(chǎng)所電氣安裝規(guī)范》。
D.通訊線:R+、R-,為RS-485信號(hào)線。
E.聯(lián)動(dòng)輸出接線:高限報(bào)警的控制輸出端子為常開觸點(diǎn)HA、HB。低限報(bào)警的控制輸出接線端子為常開觸點(diǎn)LA、LB。輸出信號(hào)為無源觸點(diǎn)信號(hào),聯(lián)動(dòng)接線線徑應(yīng)根據(jù)所連接設(shè)備的具體情況選定。
F. (4~20mA)標(biāo)準(zhǔn)信號(hào)輸出:I, 標(biāo)準(zhǔn)信號(hào)輸出端子(相對(duì)于直流電源負(fù)G)
注意:(4~20mA)標(biāo)準(zhǔn)信號(hào)輸出功能為可選配功能,定貨時(shí)必須注明。
2.3 開通
2.3.1 檢查安裝接線正確無誤后,開機(jī)。先開主電,再打開備電開關(guān);系統(tǒng)進(jìn)入預(yù)熱狀態(tài),預(yù)熱大約1分鐘后進(jìn)入檢測(cè)狀態(tài)。
注:控制器在通電后上邊的散熱風(fēng)扇自動(dòng)開啟。
3、操作說明
3.1 面板說明
3.1.1 面板示意圖(見圖4)
圖4 操作面板示意圖
3.1.2 指示燈說明(見表2)
表2 指示燈說明
|
指示燈說明 |
顏色 |
功能 |
|
報(bào)警 |
紅 |
發(fā)生報(bào)警時(shí),該指示燈亮;返回監(jiān)控態(tài)后,按復(fù)位鍵熄滅。 |
|
故障 |
黃 |
探測(cè)器存在故障時(shí),該指示燈亮 |
|
電源 |
綠 |
控制器通電時(shí),該指示燈亮 |
3.1.2 功能鍵說明(見表3)
表3 功能鍵說明
|
鍵名 |
功能 |
|
消聲|上下 |
當(dāng)控制器發(fā)生報(bào)警或故障時(shí),按下此鍵可以消除聲音報(bào)警/故障信號(hào)。上下鍵功能見具體功能說明。 |
|
復(fù)位|回車 |
按下此鍵,可使控制器所有報(bào)警/故障復(fù)位?;剀囨I功能見具體功能說明。 |
|
自檢|左右 |
當(dāng)控制器處于監(jiān)控狀態(tài)時(shí),按下此鍵,即對(duì)控制器面板指示燈、顯示器、聲報(bào)警進(jìn)行功能檢查。左右鍵功能見具體功能說明。 |
3.2 工作狀態(tài)說明
3.2.1 系統(tǒng)初始化狀態(tài)
控制器加電,控制器進(jìn)入系統(tǒng)初始化,此時(shí),濃度顯示”----”,時(shí)鐘顯示初始化進(jìn)行時(shí)間。初始化狀態(tài)大約持續(xù)60秒后,系統(tǒng)進(jìn)入監(jiān)控狀態(tài)。
3.2.2 監(jiān)控狀態(tài)
在監(jiān)控狀態(tài)下, 濃度顯示濃度值,無故障,無報(bào)警。
3.2.3 自檢態(tài)
在監(jiān)控狀態(tài)下,按自檢鍵,進(jìn)入自檢狀態(tài)。此時(shí),液晶、面板上所有的指示燈和LED都點(diǎn)亮,蜂鳴器響。
3.2.4 報(bào)警態(tài)
在監(jiān)控狀態(tài)下,如果氣體濃度超過報(bào)警濃度,控制器即進(jìn)入報(bào)警態(tài)。此時(shí)報(bào)警指示燈亮,“%LEL”顯示相應(yīng)濃度值,同時(shí)報(bào)警蜂鳴器響。功能號(hào)、報(bào)警級(jí)別顯示區(qū)顯示報(bào)警級(jí)別。報(bào)警后處理措施見<5.報(bào)警處理>。
報(bào)警級(jí)別:A1-低限報(bào)警(第1級(jí)報(bào)警)。
A2-高限報(bào)警(第2級(jí)報(bào)警)。
A3-第3級(jí)報(bào)警。
A4-第4級(jí)報(bào)警。
3.2.5 故障態(tài)
在監(jiān)控狀態(tài)下,若探測(cè)器發(fā)生故障,控制器即進(jìn)入故障態(tài)。此時(shí)故障指示燈亮,故障蜂鳴器響。
故障診斷與處理見<6.故障診斷與處理>。
3.2.6 功能態(tài)
在監(jiān)控狀態(tài)下,按回車鍵進(jìn)入功能態(tài),此時(shí)功能號(hào)顯示區(qū)閃爍,此時(shí)可以先按上下鍵再按回車鍵,切換到子功能號(hào)選擇、時(shí)鐘設(shè)置、故障記錄、報(bào)警記錄等狀態(tài),或者按左右鍵返回監(jiān)控狀態(tài)。
3.2.6.1 子功能號(hào)選擇
在本功能態(tài)下,功能號(hào)顯示焦點(diǎn)位閃爍,按左右鍵切換輸入焦點(diǎn),上下鍵改變焦點(diǎn)位數(shù)值,按回車鍵進(jìn)入子功能態(tài)(見下表4)。
表4 子功能態(tài)表
|
功能號(hào) |
功能說明 |
|
1 |
儀表地址 |
|
2 |
通訊速率 |
|
3 |
通道屏蔽 |
|
4 |
探頭類型 |
|
5 |
單位 |
|
6 |
小數(shù)位數(shù) |
|
7 |
濾波系數(shù) |
|
8 |
報(bào)警模式 |
|
9 |
報(bào)警有效性 |
|
10 |
量程上限 |
|
11 |
量程下限 |
|
12 |
報(bào)警下限(第1報(bào)警點(diǎn)) |
|
13 |
報(bào)警上限(第2報(bào)警點(diǎn)) |
|
14 |
第3報(bào)警點(diǎn) |
|
15 |
第4報(bào)警點(diǎn) |
|
16 |
死區(qū) |
|
17 |
回差 |
|
18 |
顯示更改密碼 |
|
19 |
密碼有效性 |
|
20 |
年份設(shè)置 |
|
21 |
月日設(shè)置 |
|
22 |
高報(bào)脈動(dòng)有效性設(shè)置 |
注:*-本功能無效
3.2.6.1.1 儀表地址
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:儀表地址在與上位機(jī)通訊時(shí)區(qū)分通道,有效范圍1~254。
3.2.6.1.2 通訊速率
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:儀表與上位機(jī)通訊采取”9600,n,8,1”模式,采用ModBus RTU協(xié)議。通訊波特率默認(rèn)9600,另有4800, 2400可供選擇,分別由0、1、2代表9600、4800、2400三種波特率。
3.2.6.1.3 通訊屏蔽
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:1-通道屏蔽有效,通道響應(yīng)探測(cè)器的濃度變化,但不報(bào)警;其它-無效
3.2.6.1.4 探頭類型
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。見附錄1。
3.2.6.1.5 單位
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。見附錄2。
3.2.6.1.6 小數(shù)位數(shù)
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:小數(shù)位數(shù)數(shù)值區(qū)間為0~3,默認(rèn)值0。
3.2.6.1.7 濾波系數(shù)
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:濾波系數(shù)數(shù)值區(qū)間為1~50,默認(rèn)值20。
3.2.6.1.8報(bào)警模式
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.9報(bào)警有效性
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.10 量程上限
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.11 量程下限
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.12 報(bào)警下限(第1報(bào)警點(diǎn))
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.13 報(bào)警上限(第2報(bào)警點(diǎn))
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.14第3報(bào)警點(diǎn)
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.15第2報(bào)警點(diǎn)
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.16死區(qū)
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.17回差
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
4.2.6.1.18 顯示更改密碼
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
3.2.6.1.19 密碼有效性
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)。
注:0-密碼無效;1-密碼有效,發(fā)生報(bào)警后,必須輸入密碼正確,才能復(fù)位。
3.2.6.1.20年份設(shè)置
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài),
注:本控制器的有效年份為2000~2099。
3.2.6.1.21月日設(shè)置
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)
注:濃度顯示區(qū)前兩位為月份,后兩位為日期。
3.2.6.1.22高報(bào)輸出設(shè)置
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)控態(tài)
注:濃度顯示區(qū)四位數(shù)字全為0,高報(bào)后長(zhǎng)輸出,按復(fù)位取消;否則高報(bào)脈動(dòng)輸出(閉合時(shí)間大約0.5s)。
3.2.6.2 時(shí)鐘設(shè)置
在本功能態(tài)下,按左右鍵進(jìn)入輸入狀態(tài)和改變輸入焦點(diǎn),上下鍵更改數(shù)值,按回車鍵確認(rèn),返回監(jiān)測(cè)態(tài)
3.2.6.3 故障記錄
3.3.6.4 報(bào)警記錄
4.使用調(diào)整
在檢查安裝接線準(zhǔn)確無誤后,打開電源開關(guān),控制器進(jìn)入系統(tǒng)初始化狀態(tài),大約30秒后,進(jìn)入監(jiān)控狀態(tài)。如果控制器存在故障,按《6故障診斷與處理》進(jìn)行處理。如果存在通道漂移,按《4.1通道校正》進(jìn)行調(diào)整。報(bào)警系統(tǒng)進(jìn)入正常運(yùn)行狀態(tài)。
4.1通道校正
若通道的漂移過大(超過5%F.S),則必須進(jìn)行通道校正。校正時(shí)用電流校正表,在S(+)、G(-)之間輸入4mA電流,用一字型螺絲刀調(diào)整通道零點(diǎn)調(diào)整電位器SW0,使得AB點(diǎn)之間電壓差<1mV;,在S(+)、G(-)之間輸入16mA電流,當(dāng)前濃度在75±1%LEL之間擺動(dòng)即可。
5.報(bào)警處理
5.1 在監(jiān)控狀態(tài)下,當(dāng)濃度達(dá)到低限報(bào)警濃度時(shí),控制器進(jìn)入報(bào)警狀態(tài)。當(dāng)濃度達(dá)不到低限報(bào)警濃度時(shí),按復(fù)位鍵,控制器返回監(jiān)控狀態(tài)。、
5.2在報(bào)警狀態(tài)下,按“消聲”鍵,清除報(bào)警蜂鳴聲,同時(shí)消聲指示燈亮,再按一次“消聲”鍵,消聲狀態(tài)清除,報(bào)警蜂鳴器響,消聲指示燈滅。
6.故障診斷與處理
6.1 在故障狀態(tài)下,故障指示燈亮。此時(shí)可以按“消音”鍵去除故障聲音信號(hào)。
6.2在故障狀態(tài)下, 顯示“--”說明有故障??刹扇∫韵麓胧┡懦收稀?/p>
1. 檢查控制器與探測(cè)器的連線是否正常;
2.若連線無誤,用萬用表測(cè)量S、G間電壓在0.2~1V之間.若有異常則表示探測(cè)器故障;若無異常,請(qǐng)通知本公司進(jìn)行處理。
6.3故障處理完后,可以按“復(fù)位”鍵返回監(jiān)控態(tài)。
7. 維護(hù)維修
7.1 日常維護(hù)
當(dāng)系統(tǒng)安裝完成后,在正常使用過程中,應(yīng)由專業(yè)人員每年對(duì)控制器按《4.1通道校正》
進(jìn)行調(diào)整,防止發(fā)生漂移。
7.2 若控制器達(dá)到使用年限,應(yīng)及時(shí)更換,否則容易造成零漂過大、誤報(bào)等問題,影響正常生產(chǎn)活動(dòng)。
7.3 注意環(huán)境清潔,如防塵、防水,防油煙等。
地址:北京市通州區(qū)永順西街32號(hào)
郵編:101149
:
郵箱: 
主頁:
免責(zé)聲明:以上所展示的[UC-KB-2008D UC-KB-2008D氣體報(bào)警控制]信息由會(huì)員[北京創(chuàng)偉高科電子技術(shù)有限公司]自行提供,內(nèi)容的真實(shí)性、準(zhǔn)確性和合法性由發(fā)布會(huì)員負(fù)責(zé)。